model |
np200 |
appearance
(mm) |
96(w)】96(h)】100(h) |
| function |
.retransmission output . input correction .5 time signals .constant-value control.auto/mannal output.heating/cooling .direct/reverse action.heating/cooling direct/reverse action |
power voltage power consumption input |
100~240 vac(50/60hz) less than10va(except communication) multi-input(t/c:13 kinds, valtage:3 kinds) |
|
control output |
multi-output:relay,ssr,current |
| control action |
p.i.d or on/off |
|
alarm |
4 alarm output(al-1,2,3,4) |
|
communication |
rs 485/422(optional) |
|
setting |
by up/down key on the front |
|
display |
pv:digital led, sv:lcd back light |
|
setting and display accuracy |
f.s 0.1% |
|
setting resolution |
1 or 0.1%(according to input range) |
|
memory protection |
semipermanent |
| external control |
run,reset, pattern, hold |
|
number of pattern |
30 |
| number of segment |
300 |
| number of pattern contact |
30 |
| operation |
1~99 time or limitless |
| program inclination |
hour,minute |
|
sampling cycle |
250ms |
|
insulation resistance |
500vac 20m min. |
|
dlelectric strength |
ac 2300v 50/60hz for 1 minute (between primary and secondary terminal& and ground) |
|
ambent temperature&humidity |
0~50c,20~90%rh | |
|
|
model |
hy-p100 |
hy-p101 |
|
appearance
din(mm) (w)】(h)】(d) |
96】96】160 |
96】96】160 |
|
power voltage |
100-240vac (50/60hz) |
|
power consumption |
less than 15va (except to communication option) |
|
input |
thermo couple, r·t·d, voltage/current |
|
control output |
relay contact output: ac250v(resistive load), ssr: 12vdc(constant voltage pulse) (load resistance more than 800ヘ), current: 4ma dc (load resistance less than 500ヘ) |
|
control action |
p·i·d (auto-tuning function), on/off |
|
alarm output |
indipendent variation alarm |
|
remote |
|
within rs-232c |
|
setting |
by the up/down key |
by the up/down or rs-232c |
|
display |
l.e.d display |
|
setting and indication accuracy |
【0.3% f·s + 1digit binput: within 0…399∩ 【(5% f·s + 1digit) |
|
setting resolution |
1 or 0.1 (by input range), time: 1 minute |
|
memory protection |
about 10 years |
|
external control function |
run, reset, pattern no, hold |
|
instrument accident alarm |
open collector max 24vdc 50ma - off (when make an accident) |
|
self control function |
ram check, data error check, system overcrowding check |
|
manual control |
-10…+110(resolution 1%) |
|
device control |
auto-tuning, alarm setting |
|
pattern |
6 pattern |
|
segment |
16 segment |
|
pattern contact |
until max 6 pattern |
|
operation |
999 time or limitless |
|
program |
max 1/hour |
|
sampling cycle |
500ms |
|
reverese/direct action |
be se-lected by inside switch |
|
insulation resistance |
more than dc500v 20й(between terminal and earth), more than dc 1,000v 20й(between terminal and earth) |
|
dielectric strength |
ac 500v for 1 minute (betweeh terminal and earth) ac 1,000v for 1 minute(between terminal and earth) |
|
ambient temperature and humidity |
0…50∩(32…122⒌)·35…85%rh | |
|
|
|
model |
ux100 |
|
appearance
din(mm) (w)】(h)】(d) |
48】24】100 |
|
function |
·multi input ·input correction ·protection(frong facia ip65) ·alarm output ·auto-tuning pid ·output limit correction ) ·fuzzy function ·interface(rs 485) ·reverse/direct se-lectable |
|
input |
thermocouple: k, j, e, t, r, s, b, l, n, u.wre 5-26, pl-弗 r.t.d : pt 100目, kpt 100目 direct voltage: 1…5v,1…10v,-10…20mv,0…100mv(programmable scale type) |
|
sampling time |
250ms, (when remote option: 500ms) |
|
cold junction temperature compensation tolerance |
【1.5∩(15…35∩), 【2.0∩(0…50∩) |
|
input impedance |
t/c and mv input :1 m目 min, dc v: 1m目 |
|
lead wire tolerable resistance |
r.t.d: 150目max. / wire |
|
input tolerable voltage |
【10v(t/c, r.t.d, voltage: mv dc) 【20v (voltage: v dc) |
|
noise removal rate |
nmrr(normal mode): 40db min.cmrr(common mode): 120db min, (50/60hz【1%) |
|
standard |
t/c, r.t.d: ks, iec, din |
|
scaling |
according to setting max. voltage(sh), min. value(sl) of measurement range, scaling is available(-1999…9999) |
|
standard junction temp. compensation tolerance |
【1.5∩(15…35∩), 【2.0∩(0…50∩) |
|
burn-out |
t/c : off, up/down se-lectable r.t.d: off, up/down se-lectable(detection current: 50na) |
|
accuracy |
【0.5%(full scale) | |